Simulations were carried out for concrete slabs of 20, 40 and 60 cm thickness. However, the piping of the underfloor heating system was always installed at a depth of 10 cm. The floor thickness shows only a small sensitivity with respect to the solar fraction that can be reached with the system. Doubling or even tripling the floor thickness leads to an increase in solar fraction of only a few percentage points. Therefore, a floor thickness around 30-50 cm is a reasonable value. Floor slabs in this order of magnitude are commonly used in many industrial buildings anyway.

When the results are plotted against the utilization ratio, as it was done for the system concept with storage tank, the points scatter significantly more (see Figure 6). The highest solar fractions are obtained with the standard reference case. In Case 4 (8 kW internal gains), solar fractions are lower because during the day the machine operation leads to high air temperatures and high floor temperatures, therefore the solar thermal system cannot store much heat in the concrete mass. In this case, using the thermal mass as a storage tank is particular unfavorable because the solar energy cannot be stored to be used during the night. In Case 2 (poorly insulated), solar fractions are again lower. In this case, the overall heat demand of the building is much higher and as a result the conventional heating system is turned on more often. The conventional heating system also uses the underfloor heating system, which leads to higher average floor temperatures. If this is the case, then the potential for solar heat to be stored in the floor is decreased, which in turn decreases the solar fraction that can be reached. This effect is even more pronounced in Case 1 (poorly insulated and high air exchange rate). In this case, the overall heat demand of the building is so high that the

Подпись: Figure 6. Nomogram to determine the collector area, the solar fraction and the specific collector yield. The graph is based on a concrete slab thickness of 40 cm. In Figure 6, the light-colored area shows the band of the solar fractions for solar heating systems in factory buildings that use only the concrete slab as heat store. The light-colored area excludes Case 1 because the simulation results have shown that using only the thermal mass as heat store for buildings with very high heat demands does not make sense. The specific collector yields can be significantly higher compared to the cases where a storage tank was used. The reason for this is that the control strategy for thermal mass usage “overheats” the building to a certain extent. This does not necessarily decrease the auxiliary heat demand.

conventional heating system has to be turned on almost all the time. Therefore, solar fractions are decreased dramatically.

Regarding the nomogram for systems using the concrete slab as heat store, it is even more important to remember that the results shown can only give a rough approximation of the solar fractions that can be reached. The results are only strictly valid for the reference buildings described above. Systems without water store are even more sensitive to a change of boundary conditions as could be shown with the different reference cases considered. If for example, a building is much higher than the reference buildings or a higher air temperature is required, this can have a strong influence on the function of the concrete slab as a heat store. It not only increases the heat demand of the building but also decreases the solar fraction that can be reached. Therefore, a more detailed simulation of the building and the heating system may be necessary if the thermal mass is to be used as the only heat store.

As for systems that use a water storage tank, systems should be designed in accordance with the optimum cost-to-benefit ratio (orange area, degrees of solar fraction of the overall heating requirement between 15 and 30%). Degrees of solar fraction of less than 15% are outside the cost- to-benefit optimum since the (slight) rise in the specific yield does not make up for the higher specific system costs of a smaller solar thermal system and would thus lead to higher solar heating costs.

EuroSun2008-2

Validation of the library components

The validation of the models is necessary to ensure that the calculated results are valid. Furthermore it is to proof what differences consist due to the assumptions made in the …

Solar industrial process heat plants in operation

Data gathered in the framework of the IEA Task 33/IV include comprehensive information about the geographical distribution of the solar thermal plants, the industrial sectors addressed, the specific processes, the …

Experimental Investigations On Solar Driven Desalination Systems Using Membrane Distillation

J. Koschikowski*, M. Wieghaus*, M. Rommel*, Vicente Subiela Ortin**, Baltasar Penate Suarez**, Juana Rosa Betancort Rodriguez** * Fraunhofer Institute for Solar Energy Systems ISEHeidenhofstr.2,79110 Freiburg, GermanyTel +49-761-4588-5294Fax +49-761-4588-9000email ioako@ise. fhg. …

Как с нами связаться:

Украина:
г.Александрия
тел./факс +38 05235  77193 Бухгалтерия

+38 050 457 13 30 — Рашид - продажи новинок
e-mail: msd@msd.com.ua
Схема проезда к производственному офису:
Схема проезда к МСД

Партнеры МСД

Контакты для заказов оборудования:

Внимание! На этом сайте большинство материалов - техническая литература в помощь предпринимателю. Так же большинство производственного оборудования сегодня не актуально. Уточнить можно по почте: Эл. почта: msd@msd.com.ua

+38 050 512 1194 Александр
- телефон для консультаций и заказов спец.оборудования, дробилок, уловителей, дражираторов, гереторных насосов и инженерных решений.