CONTROL ROOM DESIGN AND ERGONOMICS

Open and Closed Controls

In open control, the control equipment is not affected by the object or process. Cer­tain types of control equipment in central heating systems are examples of open con­trol (see Figure 2.9). The control equipment has the job of reducing the temperature in the water used for heating at night, according to a preset programme. The measur­ing device, for example, senses by means of electrical contacts switched on or off by pegs from the control device, the stage in the programme that has been reached. The contacts ‘inform’ the central link, which processes the information. After pro­cessing, certain of the input conditions given by the measuring device will result in a command to the control device (for example, to start valve motor 1). Note that no signal from the process/control object affects the control equipment.

It is very difficult using open control to maintain the actual value at the set value. This can only happen when the object is not exposed to any external disturbances, or where these are well known and can be taken into account in advance. Where these conditions are not met, large deviations from the desired values must be allowable in order for open control to be used.

Closed control (see Figure 2.10) has a system where the output signal (actual value) is fed back to the input signal (desired value) and compared with it. The input signal is, in certain cases, the desired output signal. When this required actual value, the desired value, is compared with the true value fed back, a difference results if the actual value deviates from the set (desired) value. After amplification via the control device, this deviation then goes in as the control quantity to control the process or object.

Disturbance

Quantity

Open and Closed Controls

FIGURE 2.9 Open control: Note that there is no feedback from the output of the controlled object to the controller, but only within the controller itself. Changes in the controlled quan­tity thus cannot affect the control equipment.

Open and Closed Controls

FIGURE 2.10 Closed-loop control, also known as regulation. The regulated quantity affects the controlling signal.

The controlled system is also affected by external disturbances (yn). The signal (yO) goes out from the system, is measured, and fed back.

When the comparison between the input (y) and the feedback signal is an addi­tive, this is known as positive feedback. This type of feedback, which gives an accelerating change of the output signal, is used, for example, to achieve the fastest possible changes of output signal. When the comparison between y and yO is subtrac­tive, we have negative feedback. This means that yd (difference quantity) decreases when the output yO increases, and thus attempts to stop yO rising. Negative feedback is the most common form of feedback. One well-known example of a control mecha­nism with negative feedback is the regulation of the water level in a WC cistern by a ball-cock valve. Figure 2.11 shows a diagram of a cistern with its ball-cock valve and the corresponding signal control diagram (a block diagram).

A distinction may be made between closed control systems,[3] which only have to compensate for outside disturbances and not for changing inputs, and closed control systems which are not exposed to outside influences but which only attempt to follow changes in input quantity. The first type of regulation system (where the input value is not changed) is known as constant regulation. The second type, with variable inputs, is known as servo-regulating. A servo-regulating system only has the task of trying to achieve an output that follows as closely as possible the varying input level. The WC cistern described above is an example of constant regulation, which tries to keep the output (in this case, the water level) constant regardless of outside disturbances (that is, the water being flushed out of the cis­tern). Most regulation systems in process industries function as constant regula­tion systems (where the set value can be changed). At start-up, however, a certain degree of servo-regulation takes place.

Open and Closed Controls

Open and Closed Controls

Quantity (yn) Regulated

Open and Closed Controls

FIGURE 2.11 Regulation of water level using a float valve (constant regulation).

 

CONTROL ROOM DESIGN AND ERGONOMICS

Levers

Levers are activated either by the whole hand or just by the fingers. In general, where fine control is needed, only the fingers should be used. The following recommendations apply …

Rotary Switches

These can be divided into two categories: cylindrical and winged. The primary dif­ference between these is that the winged version has a pair of ‘wings’ above the cylindrical part. The …

Toggle Switches

Toggle switches can be used to show two or three positions. Where there are three positions, one should be up, the middle one straight out, and the other one down­wards. …

Как с нами связаться:

Украина:
г.Александрия
тел./факс +38 05235  77193 Бухгалтерия

+38 050 457 13 30 — Рашид - продажи новинок
e-mail: msd@msd.com.ua
Схема проезда к производственному офису:
Схема проезда к МСД

Партнеры МСД

Контакты для заказов оборудования:

Внимание! На этом сайте большинство материалов - техническая литература в помощь предпринимателю. Так же большинство производственного оборудования сегодня не актуально. Уточнить можно по почте: Эл. почта: msd@msd.com.ua

+38 050 512 1194 Александр
- телефон для консультаций и заказов спец.оборудования, дробилок, уловителей, дражираторов, гереторных насосов и инженерных решений.